Mist cooling system installation

Installation

Misting fan:

The cooling, misting or humidification effects depend on the sizes of misting fans, nozzle sizes, spacing between nozzles and the relative humidity.

Spacing:

Standard spacing between nozzles ranges from 0.5 to 1.5 meter. Standard spacing between pipelines is determined by nozzle output and the desired humidity to be created.

Pumps and Nozzles

The choices of pumps and nozzles are determined by the size of the installation size, the requirements of cooling, misting, and humidification effects and the humidity in the air.

Pump:

The pump is determined by the number and size of nozzles used. For example, if the flow of a nozzle is 46cc/min and there are three hundred nozzles used, then the total volume of water required per minute is 13,800cc (46 x 300). Please use a pump with a minimum output volume of 13.8liters per minute. Generally, a pump with pressure more than 70kgf/cm^2 will achieve the best results.

Nozzles:

For best fogging effects, choose nozzles with small orifice sizes to reinforce cooling effects and to avoid dripping. This also helps to increase the negative ions in the air.

Maintenance

Nozzle:

Put nozzle in a container with 70c water and use mineral deposit dissolver to soak the nozzles for 4 hours; then, use an ultrasonic cleaner to clean the nozzle.


  • On-site installation
  • Adjustable nozzle angle
  • Easy maintenance
  • Durable design, resists chemicals and UV rays